Code Compliance
Load Capacity
Australia
Crosstrack integrated access flooring when correctly installed onto a satisfactory sub-floor will meet the strength requirements of the Building Code of Australia as defined in AS1170.1 minimum design loads on structures. Crosstrack-performs against these requirements as follows:
The assembled tile module
Code requirement |
Crosstrack |
uniformly distributed live load |
>7.5 kPa >500 kPa |
concentrated live load |
>6.7 kN 9.0 kN |
International
Crosstrack standard grade meets relevant performance criteria equivalent to Medium Structural Grade flooring for pedestal supported platform floors as defined in Australian Standard AS4154 (1933) and the UK access floor Standard MoB PF2 PS (1992). Enhanced grades are available with loading performance equivalent to Heavy and Extra Heavy Structural grades.
Fire Performance
Australia
Crosstrack integrated access flooring meets the Early Fire Hazard Indices required by the Building Code of Australia, which are defined in AS1530.3 methods for fire test on building materials, components and structures, as follows:
BCA Limit |
"Crosstrack" |
base |
deck |
Ignitability (range 0-20) |
no requirement |
8 |
13 |
Heat Evolved (range 0-10) |
no requirement |
2 |
6 |
Spread of Flame (range 0-10) |
<9 |
3 |
8 |
Smoke developed (range 0-10) |
<8 |
5 |
3 |
International
The Crosstrack standard base passes British Standard BS 476 Part 5.
Decomposition products are primarily CO2 and H2O Flame retardant grades are available for specific applications which meet US Standard UL94 V2.
Deck panels are available which meet Class 1 flame spread as defined in British Standard BS 476 Part 7.
|